AS 4773:2015 masonry in small buildings: builder's guide
AS 4773:2015 is the go-to masonry standard for Class 1 houses. Covers geometric limits, ties, articulation joints, cavity and veneer walls under NCC 2022 H1D5.
Ask Chalkline about this →TL;DR
AS 4773 (Parts 1 and 2, both current at 2015 edition) is the practical masonry standard for Class 1 houses and Class 10a garages. It sits inside the geometric limits that cover the overwhelming majority of residential builds: eaves height no more than 6.0 m, overall roof height no more than 8.5 m, building width no more than 16 m. If your job is within those bounds, AS 4773 plus the ABCB Housing Provisions 2022 (Section 5, free at ncc.abcb.gov.au) is the DTS path under NCC 2022 H1D5 without needing a structural engineer to design to the heavier AS 3700. Where AS 4773 limits are exceeded (taller buildings, Class 2 apartments, complex reinforced masonry), the job steps up to AS 3700 and typically needs an engineer. The most common site failures on AS 4773 jobs are missing or filled articulation joints, cavity not kept clear of mortar droppings, and ties at the wrong duty for the wind class.
In plain English
AS 4773 was developed specifically for masonry in houses and similar small structures. It was last published in 2015 (both parts incorporating Amendment No. 1 from November 2016) and remains the current edition (verified 2026-05-08, Standards Australia AS 4773.1:2015 and AS 4773.2:2015).
The standard comes in two parts:
- AS 4773.1:2015: Design. Covers masonry wall design, wall tie selection, articulation joint requirements, mortar specification, lintel sizing, and the geometric limits.
- AS 4773.2:2015: Construction. Covers workmanship on site, material handling, laying practices, control joints, cavity management, and built-in components.
AS 4773 applies to clay brick, concrete masonry, and calcium silicate (sandlime) masonry units with a leaf thickness of 90 mm or greater. It does not cover autoclaved aerated concrete (AAC) blocks, which are addressed under AS 5416.
The companion standard AS 3700:2018 covers all masonry structures, including the complex and larger-scale work outside AS 4773’s limits. For most residential jobs, AS 4773 is simpler and sufficient.
What it requires
NCC 2022 reference point
NCC 2022 Volume Two Clause H1D5 states that masonry in Class 1 and Class 10 buildings must be designed and constructed in accordance with either:
- AS 3700, or
- AS 4773.1 and AS 4773.2
Both are DTS paths. The ABCB Housing Provisions Standard 2022, Section 5 (Masonry) provides the same DTS rules in an accessible format and is free at ncc.abcb.gov.au (verified 2026-05-08, NCC 2022 Volume Two H1D5).
The Housing Provisions’ wind and site constraints mean AS 4773 via that pathway applies only where wind class does not exceed N3 and the site is classified A, S, or M under AS 2870. If your site is class H, E, or P, or in a cyclonic area above N3, you need engineered design.
Geometric limits of AS 4773
AS 4773 applies where the building geometry stays within all of the following limits (verified 2026-05-08, AS 4773.1:2015 Clause 1.2.2):
| Parameter | Maximum limit |
|---|---|
| Eaves height above ground | 6.0 m |
| Highest roof point above ground (excluding chimneys) | 8.5 m |
| Building width (including roofed verandas, excluding eaves) | 16.0 m |
| Building length | 5 times the width |
| Individual storey height (floor to ceiling at external wall) | 3.0 m |
| Roof pitch | 35 degrees |
| Eaves width | 900 mm |
If any of these limits is exceeded, the masonry design steps up to AS 3700 and an engineer of record is required.
Masonry types and wall height limits
The Housing Provisions set the following maximum wall heights for the DTS path (verified 2026-05-08, NCC Housing Provisions 5.2 and 5.3):
| Masonry type | Maximum wall height above finished ground |
|---|---|
| Masonry veneer | 8.5 m |
| Cavity masonry | 8.5 m |
| Unreinforced single leaf external | 3.0 m between lateral supports |
For cavity masonry, the wall between lateral supports must not exceed 3.0 m in height. Cross walls providing lateral support must be at least 2.0 m long and spaced no more than 5.1 m apart. Each masonry leaf must be at least 90 mm thick. The cavity must be 35 mm to 75 mm clear width.
For masonry veneer, the cavity between the veneer leaf and the frame backing must be 25 mm to 75 mm clear width. Mortar droppings (snots) that fall into the cavity and bridge the gap are the most common cause of cavity failure.
Wall ties (Housing Provisions 5.6.5)
Wall ties must comply with AS 2699.1 and be selected to match the wind class and masonry type. The minimum duty ratings from the Housing Provisions (verified 2026-05-08, NCC Housing Provisions 5.6.5):
| Masonry type | Wind class | Minimum tie duty |
|---|---|---|
| Masonry veneer | N2 or below | Light duty |
| Masonry veneer | Above N2 | Medium duty |
| Cavity masonry | N1 | Light duty |
| Cavity masonry | Above N1 | Medium duty |
Maximum tie spacing: 600 mm horizontally and vertically for cavity masonry. For veneer with 450 mm stud spacing, maximum 450 mm horizontal and 600 mm vertical. For veneer with 600 mm stud spacing, maximum 600 mm horizontal and 400 mm vertical.
Critical fixing positions: ties must be placed within 300 mm of panel edges and openings, within 300 mm or two courses (whichever is less) of the top and bottom of any veneer panel, and within the first two courses at DPC level. Ties must embed at least 50 mm into each masonry leaf.
Corrosion protection requirements increase with coastal exposure:
| Location | Minimum protection |
|---|---|
| Within 1 km of breaking surf, within 100 m of salt water, or heavy industrial | Grade 316L stainless steel or engineered polymer |
| 1 km to 10 km from breaking surf, 100 m to 1 km from salt water | 470 g/m2 hot-dip galvanised post-manufacture, or Grade 304L stainless |
| All other areas | 300 g/m2 galvanised coating |
Articulation joints (Housing Provisions 5.6.8)
Articulation joints are vertical movement control joints built into masonry walls to accommodate thermal expansion, moisture change, and foundation movement. They must have a minimum width of 10 mm and be filled with flexible sealant backed by compressible foam or a purpose-made backer rod.
Spacing rules (verified 2026-05-08, NCC Housing Provisions 5.6.8):
| Wall condition | Maximum joint spacing | Placement note |
|---|---|---|
| Straight wall, openings under 900 mm x 900 mm | 6 m centres | Within 4.5 m of corners; not closer than 470 mm to a corner |
| Straight wall, openings 900 mm x 900 mm or over | 5 m centres | Within 1.2 m of any opening |
| At wall height changes exceeding 20% | At the change point | Continuous through the full leaf height |
| At thickness changes, footing joints, or material junctions | At the change point | Continuous |
Exception: articulation joints are not required on sites with soil classification A or S under AS 2870.
The joint must be continuous through the full height of the masonry leaf. Partial joints, mortar-filled joints, or joints that are bridged at any course level provide no movement capacity and will cause diagonal cracking. This is the defect most commonly missed on site.
Mortar mixes (Housing Provisions 5.6.3)
Mortar proportions by volume (cement:lime:sand) depend on exposure class (verified 2026-05-08, NCC Housing Provisions 5.6.3):
| Exposure class | Clay/calcium silicate masonry (cement:lime:sand) | Concrete masonry (cement:lime:sand) |
|---|---|---|
| Protected (internal or coated external) | 1:2:9 | 1:0:5 |
| General purpose | 1:1:6 | 1:0:5 |
| Exposure (salt attack zones) | 1:0.5:4.5 | 1:0:4.2 |
Nominal bed and perpend joint thickness is 10 mm. Raked joints are not allowed in saline or heavy pollution environments. Maximum raking depth is 5 mm for units 90 mm wide, and 10 mm for units 110 mm wide.
Masonry workmanship tolerances
The maximum permitted deviation for finished brickwork plumb and straightness in residential construction is pending verified member access to the HIA Guide to Materials and Workmanship. [HIA-060]
AS 4773.2:2015 itself includes workmanship tolerances for the construction phase (setting out, levelling, courses), but the post-completion acceptance tolerances for a builder’s practical inspection use the HIA Guide values. State Guides to Standards and Tolerances (e.g. Victoria’s Guide) are partially public; check your state regulator’s website for what is accessible before the HIA tracker is resolved.
What it doesn’t cover
AS 4773 does not apply to:
- Class 2 buildings (apartments): must use AS 3700 with engineer design
- Class 5 to Class 9 buildings (commercial): covered by NCC Volume One and AS 3700
- Buildings outside the geometric limits in Clause 1.2.2: step up to AS 3700
- Autoclaved aerated concrete (AAC) blocks: covered by AS 5416, not AS 4773
- Earth masonry (rammed earth, mud brick): not covered; performance solution required
- Masonry retaining walls not associated with a building: separate structural design
Practical implications
Choosing AS 4773 versus AS 3700 on a house
For a standard Class 1 house or townhouse sitting within the 6.0 m eaves height and 16.0 m width limits, AS 4773 is the right DTS path. The brickie and the builder use the Housing Provisions (Section 5) as the day-to-day working document; AS 4773 is the nominated standard backing those provisions.
AS 3700 applies when:
- The building is Class 2 (apartments) or the engineer has been engaged for a specific reason
- Any geometric limit in AS 4773 Clause 1.2.2 is exceeded
- The masonry is complex (large reinforced piers, prestressed elements, unusual loads)
- The certifier or structural engineer specifies AS 3700 by reference
On most suburban residential builds, the builder will never open AS 4773 directly. The Housing Provisions are the accessible document. AS 4773 is the backstop that Housing Provisions compliance relies on.
Sequencing on site
The critical construction sequence for masonry compliance on a house:
- Footings and slab complete, DPC laid at base course level before the first brick goes down
- First course laid to line, weep holes formed at DPC level (maximum 1.2 m centres)
- Cavity kept clear of mortar droppings throughout, especially in the lower courses where snots accumulate fastest
- Wall ties placed at correct centres and duty as the inner frame rises; critical positions at DPC, at openings, and at panel edges
- Articulation joints formed at designed locations, continuous through the full leaf height, backed with compressible foam
- Flashings and DPC installed above openings and at roof abutments before masonry continues
- Weep holes formed immediately above each flashing course
- Mortar mix matched to exposure class; raked joints avoided in coastal locations
Common defects under AS 4773
These failures show up repeatedly in building inspections and warranty claims:
| Defect | Cause | Impact |
|---|---|---|
| Articulation joints filled or missing | Not formed, or later filled with mortar snots | Diagonal cracking as thermal movement accumulates |
| Articulation joints not continuous | Stopped partway up the wall height | Partial movement only; cracking resumes above the stopped point |
| Cavity bridged by mortar droppings | Not cleaned during construction | Moisture path across cavity; rising damp; tie corrosion |
| Cavity width outside 25 mm to 75 mm range | Inconsistent frame or brick setting out | Ties overstressed (too wide) or mortar bridging (too narrow) |
| Ties wrong duty for wind class | Light duty in exposed coastal or high-wind locations | Veneer detachment risk in high-wind events |
| DPC below 150 mm above ground | Set too low, or ground built up after construction | Rising damp pathway into wall cavity |
| Weep holes blocked or missing | Snots at base course; not formed above lintels | Moisture ponds in cavity; potential corrosion of lintels and ties |
| Wrong mortar mix for exposure class | Protected mix used in coastal/saline locations | Accelerated mortar degradation; joint failure |
Source link
Standards Australia store: AS 4773.1:2015 and AS 4773.2:2015 (verified 2026-05-08). Both parts are paywalled. The free working document is the ABCB Housing Provisions 2022, Section 5 Masonry.
References
- Standards Australia, AS 4773.1:2015 (incorporating Amendment No. 1) Masonry in small buildings, Part 1: Design. https://store.standards.org.au/product/as-4773-1-2015 (verified 2026-05-08).
- Standards Australia, AS 4773.2:2015 (incorporating Amendment No. 1) Masonry in small buildings, Part 2: Construction. https://store.standards.org.au/product/as-4773-2-2015 (verified 2026-05-08).
- Australian Building Codes Board, NCC 2022 Volume Two, Part H1 Structure, Clause H1D5 Masonry. https://ncc.abcb.gov.au/editions/ncc-2022/adopted/volume-two/h-class-1-and-10-buildings/part-h1-structure (verified 2026-05-08).
- Australian Building Codes Board, ABCB Housing Provisions Standard 2022, Section 5 Masonry. https://ncc.abcb.gov.au/editions/ncc-2022/adopted/housing-provisions/5-masonry (verified 2026-05-08).
- Australian Building Codes Board, ABCB Housing Provisions Standard 2022, Part 5.6 Masonry components and accessories. https://ncc.abcb.gov.au/editions/ncc-2022/adopted/housing-provisions/5-masonry/part-56-masonry-components-and-accessories (verified 2026-05-08).
Related
- AS 3700:2018 masonry structures, the parent standard that AS 4773 sits within and steps up to for complex or larger buildings
- NCC 2022 Volume Two, the residential building code that calls up AS 4773 under H1D5 Structure
- Brickie (trade), what a bricklayer covers, licensing, tolerances, and what to require in their quote
- NCC structure, BCA and PCA, how the structural performance requirements sit within the NCC framework
- Articulation joint, the vertical movement control joint required by Housing Provisions 5.6.8
- Cavity masonry, double-leaf masonry with a clear cavity between leaves
- Masonry veneer, single masonry leaf tied to a structural backing frame
See also
- Weep hole, open perpend above DPC that drains the cavity
- Perpend, the vertical mortar joint between bricks
- AS 1684 residential timber-framed construction, the timber framing standard on the same residential build
- AS 2870 residential slabs and footings, the footing standard underpinning masonry walls
Last updated: 2026-05-08. Verified: 2026-05-08. Quarterly review for currency: confirm AS 4773:2015 is still the current edition and check NCC adoption status in each state.